Sizing of Under Ground and Over Head water tanks.


The availability of continuous running tap water is a luxury in our country. This article deals with the sizing of domestic and flushing water tanks only. It does not deal with rain water harvesting tanks or solar water tanks.
Domestic water consumption in our country is increasing as the population moves more and more to the cities. Buildings and housing complexes have a high density of population in a small area and hence the systems for the water supply in these complexes need to be properly designed. The sizing of the Under Ground Tanks (UGT) and the Over Head Tanks (OHT) has to be done properly. The sizing is also based on the balance between the civil costs of the construction and the amount of time the pumps have to run to fill these tanks.
The National building code of India provides guidelines on the calculation of the water demand and the sizing of water tanks. The quantity of water to be stored shall be calculated taking into account the following factors:

  • ·         Hours of supply at sufficiently high pressure to fill up the overhead storage tanks;
  • ·         Frequency of replenishment of overhead tanks, during the 24 h;
  • ·         Rate and regularity of supply; and
  • ·         Consequences of exhausting storage particularly in case of public buildings like hospitals.
 The first step to the design of the tanks is calculating the water demand of the building/housing complex.
The water demand shall be calculated as per the guidelines of NBC. It is recommended to take the lower limit of 150 litres/person/day.The split of domestic and flushing water is as follows.

Domestic water – 105 lpd and flushing water – 45 lpd

The number of people (population) in a building complex has to be provided by the architect on the basis of the utilisation of the building. The total water requirement can hence be calculated.

Total domestic water = population x 105   ---- (a)

Total flushing water = population x 45    ---- (b)

This gives the daily demand of water required (a) + (b).

This is divided on the following basis; 1/3rd  day storage in the OHT and 2/3rd storage in the UGT. The storage in the UGT may be increased upto 1.5 times if the above factors are relevant and need to be accounted for.

All other water requirements have to added to this to arrive at the total storage capacity
1.       Fire fighting storage
2.       Irrigation water requirement
3.       Make up water for water bodies.
4.       Make up water for cooling towers if any.

The sum totals of these requirements are to be calculated separately for the UGT and OHT.

Considering a water depth around 2 to 2.5 m the size of the tank can be calculated .

References : NBC PART 9 PLUMBING SERVICES — SECTION 1 WATER SUPPLY, DRAINAGE AND SANITATION

Any comments and suggestions are welcome. 

Saturday, 31 January 2015

Sizing of backup generators in residential buildings


The requirement of backup generators for buildings and their sizing is a much debated topic.  It is a compromise between the economics of cost and the need for continued availability of power. The general tendency is to size the generator on the basis of experience of smaller buildings where it is provided as an afterthought. This makes it difficult for the MEP team to justify the size requirement for the generator.

In modern high rise buildings generator backup is required for the following:
1.       Lifts.
2.       Water supply pumps.
3.       Sewage treatment plant.
4.       Fire pump; if the backup pump is also electrical.
5.       Emergency lighting.
6.       Any other loads deemed necessary.

The loads in the list above can be segregated into two types,
Essential loads – These loads do not need immediate power backup, but require power in case of extended power failure.
Life safety systems – These systems need to have immediate power backup, extended power failure can have serious effect.

Of the above items 4 and 5 are life safety services.

The straight forward method of sizing a generator can be done in the following steps
1.       Make a list of all the equipments to be fed by the generator with the electrical loads and demand load for each item.
2.       Segregate the load into two columns for the following two conditions
·         Power failure condition.
·         Fire condition
3.       Find the higher load of the two.

The generator is to be sized to cater to the larger load.

A sample table shown below can help in making the decision regarding the sizing as well as the basis of the decision for record. The loads are listed in column 3 and they are copied to columns 4 or 5 as per the type of load.

Sl.No
Load
kW
Essential
Life Safety
1
Lift -1
15
15

2
Lift -2
15
15

3
Lift - 3 - Fire lift
15
15
15
4
Service lift
20
20

5
Water supply



6
Domestic Water Pump
10
10

7
Flushing water pump
7.5
7.5

8
Sewage treatment plant
45
45

9
Fire pumps
70

70
10
Jockey pump
5
5

11
Emergency lighting
5
5
5






Total

137.5
90

In the case above, the load on the generator will be 137.5 kW.  



So the next largest size of generator should be chosen. 

 Hope the same is helpful. Do let me know your comments and suggestions on the method above.



--X--